Conettix D6600 Manual do Utilizador Página 45

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 185
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 44
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
.
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
45
3.2.2 Ademco Contact-ID (Message Type a)
Contact-ID
Example
SIA Mode Description
<LF><CRC><a><sequence#><receiver#><line#>[#aaaa|18QXYZGGCCC]<CR>
Table 43: Ademco Contact-ID (Message Type a) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type a
sequence# The message sequence number. The valid sequence number range is
0001 to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the
message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for
internal messages.
account# The communicator's account number has four digits.
18 Ademco Contact-ID format number.
Q Qualifier, 1 = New event or opening, 3 = New restore or closing, 6 =
Previous event.
XYZ Class code and event code (refer to Appendix A: Contact ID Event Code
Classifications).
GG Group number.
CCC Zone codes or User ID.
Figure 8: Message sent to printer
mm/ddshh:mmsLxxsCIDsACCTsaaaa
+++sACCTsaaaasNNNsEVENT=XYZsG=GGsC=CCC
For lines that are
grouped, Gxx appears instead of Lxx.
Table 44: Ademco Contact-ID (Message Type a) Printer Output
Characters Description
CID
Contact-ID format.
Gxx Grouped Line numbers.
Lxx
Line number.
NNN
If Q = 1, print E/O for new event or opening If Q = 3, print R/C for restore or c
losing
If Q = 6, print “OLD” for old messages and events.
Vista de página 44