Conettix D6600 Manual do Utilizador Página 67

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 185
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 66
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
.
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
67
3.2.22 Sescoa Super Speed (Message Type 7)
Sescoa Super
Speed
Example
SIA Mode Description
<LF><CRC><7><sequence#><receiver#><line#>[#aaaa| IAAC]<CR>
Table 78: Sescoa Super Speed (Message Type 7) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type 7
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
account# The communicator's account number has four digits.
I Event code.
AA Two- digit zone code or the first two digits user code.
C Space if zone report, or the last digit user code.
Figure 23: Message sent to printer
mm/ddshh:mmsLxxSESsACCTsaaaa +++sACCTsaaaasEEEseeeeeeeeeeeeee
For lines that are grouped, Gxx appears instead of Lxx.
Table 79: Sescoa Super Speed (Message Type 7) Printer Output
Characters Description
SES SESCOA Super Speed format.
Lxx Line number.
Gxx Grouped line numbers.
aaaa Account code.
EEE SESCOA Super Speed format event.
eeeeeeeeeeee
ee
Up to 14-characters of event description.