Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
.
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
53
3.2.10 Common Formats (Message Type <TAB>)
Defined
Messages SIA
Example
SIA Mode Description
<LF><CRC><TAB><sequence#><receiver#><line#>[#aaaaaaaaaaaaaaaa|data]<CR>
Table 56: Common Formats (Message Type <TAB>) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical Redundancy Check number.
Message Type 09 hex <TAB>
sequence# The message sequence number. The valid sequence number range is
0001 to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the
message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for
internal messages.
account# The communicator's account number up to sixteen digits.
Data This field contains message data codes such as event type, area number,
point number, identification number, and so on.
The receiver gateway sends the 3-1, 4-1, 4-2, single round, double round, extended pulse formats,
BFSK, Modem II or Modem IId messages in either D6500 Mode or SIA Mode, depending on the
program option selected. The receiver gateway also sends internal and ModemIIIa² messages in either
D6500 mode or SIA mode, depending on the programmable option selected. Refer to Appendix B:
Internal Messages and Appendix C: Modem4/ModemIIIa² for a list of the messages and their
descriptions.
Figure 14: Message sent to printer
MM/DDsHH:MMsLxxSIA ACCT aaaa
+++ TEXT 1
+++ TEXT 2