Conettix D6600 Manual do Utilizador Página 52

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 185
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 51
Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
52
3.2.9 CFSK (Message Type i)
CFSK Example SIA Mode Description
<LF><CRC><I><sequence#><Receiver#><line#>[#aaaaaa|TTEE]<CR>
Table 55: CFSK (Message Type i) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type i.
sequence# The message sequence number. The valid sequence number range is
0001 to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
account # The communicator's account number, up to six digits.
TT Event code.
EE Zone/User ID.
Vista de página 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 184 185

Comentários a estes Manuais

Sem comentários